Unit Specifications
The following table provides electrical and refrigeration specifications for the NE050, NE060 & NE080 Series Air Conditioners.
Nominal Capacity Rating: 5,000 BTUH
Standard Maximum Ambient: 125°F
Unit Weight: 100lbs (120/230VAC) / 140lbs (480VAC)
Model | Operating Voltage Range
(Volts) |
Inrush Current (Start Up Current) (Amps) |
Loading Current (Running Current) (Amps) |
SCCR (Short Circuit Current Rating) (Amps) |
Recommended Fuse Selection
(Amps) |
KVA Rating
(K-Watts) |
Refrigerant Type | Refrigerant Amount
(ounces) |
Low/High Unit Pressures
(psi) |
NE050126 | 110-120 | 23.42 | 7.26 | *2 | 12 Amp Class CC, CCMR Time Delay * | 0.85 | R422d | 12.50 | 188 / 300 |
NE050236 | 220-240 | 19.15 | 3.76 | *2 | 10 Amp Class CC, CCMR Time Delay * | 0.7 | R422d | 12.50 | 188 / 390 |
NE050486 | 440-480 | 9.18 | 1.44 | 160K | 5 Amp Class CC, CCMR Time Delay * | 0.7 | R422d | 12.50 | 188 / 390 |
* Time-delay Fuses with the following electrical characteristics are recommended. Fast-acting fuses are not recommended.
% of Ampere Rating | Opening Time |
110 % | 15min Minimum |
125 % | 1hr Maximum |
200 % | 12sec Minimum 4min Maximum |
*2 SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.
NE060 Series
Nominal Capacity Rating: 6,000 BTUH
Standard Maximum Ambient: 125°F
Unit Weight: 100lbs (120/230VAC) / 140lbs (480VAC)
Model | Operating Voltage Range
(Volts) |
Inrush Current (Start Up Current) (Amps) |
Loading Current (Running Current) (Amps) |
SCCR (Short Circuit Current Rating) (Amps) |
Recommended Fuse Selection
(Amps) |
KVA Rating
(K-Watts) |
Refrigerant Type | Refrigerant Amount
(ounces) |
Low/High Unit Pressures
(psi) |
NE060126 | 110-120 | 42.41 | 7.83 | *2 | 25 Amp Class CC, CCMR Time Delay * | 1.0 | R422d | 18.00 | 188 / 340 |
NE060236 | 220-240 | 21.15 | 4.80 | *2 | 12 Amp Class CC, CCMR Time Delay * | 0.9 | R422d | 18.00 | 188 / 410 |
NE060486 | 440-480 | 10.13 | 1.80 | 160K | 5 Amp Class CC, CCMR Time Delay * | 0.9 | R422d | 18.00 | 188 / 410 |
NE080 Series
Nominal Capacity Rating: 8,000 BTUH
Standard Maximum Ambient: 125°F
Unit Weight: 100lbs (120/230VAC) / 140lbs (480VAC)
Model | Operating Voltage Range
(Volts) |
Inrush Current (Start Up Current) (Amps) |
Loading Current (Running Current) (Amps) |
SCCR (Short Circuit Current Rating) (Amps) |
Recommended Fuse Selection
(Amps) |
KVA Rating
(K-Watts) |
Refrigerant Type | Refrigerant Amount
(ounces) |
Low/High Unit Pressures
(psi) |
NE080126 | 110-120 | 42.41 | 7.83 | *2 | 25 Amp Class CC, CCMR Time Delay * | 1.0 | R422d | 19.00 | 188 / 345 |
NE080236 | 220-240 | 21.15 | 4.80 | *2 | 12 Amp Class CC, CCMR Time Delay * | 0.9 | R422d | 19.00 | 188 / 410 |
NE080486 | 440-480 | 10.13 | 1.80 | 160K | 5 Amp Class CC, CCMR Time Delay * | 0.9 | R422d | 19.00 | 188 / 410 |
* Time-delay Fuses with the following electrical characteristics are recommended. Fast-acting fuses are not recommended.
% of Ampere Rating | Opening Time |
110 % | 15min Minimum |
125 % | 1hr Maximum |
200 % | 12sec Minimum, 4min Maximum |
*2 SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.