Unit Specifications
The following table provides electrical and refrigeration specifications for the HC201 Series Air Conditioners.
Nominal Capacity Rating: 20,000 BTUH
Standard Maximum Ambient: 131°F
Model | Operating Voltage Range
(Volts) |
Inrush Current (Start Up Current) (Amps) |
Loading Current (Running Current) (Amps) |
SCCR (Short Circuit Current Rating) (Amps) |
Recommended Circuit Protection (Amps) |
KVA Rating
(K-Watts) |
Refrigerant Type | Refrigerant Amount
(ounces) |
Low/High Unit Pressures
(psi) |
Noise Level (dBA) |
Weight (Unit/Ship (lbs) |
HC201236 | 207-253 | 51.50 | 13.7 | *2 | 25 Amp Class CC, CCMR Time Delay * | 3.1 | R407f | 42 | 140 / 397 | n/a | 205/226 |
HC201486 | 440-480 | 24.68 | 6.56 | 160K | 12 Amp Class CC, CCMR Time Delay * | 3.1 | R407f | 42 | 140 / 397 | n/a | 320/342 |
* Time-delay Fuses with the following electrical characteristics are recommended. Fast-acting fuses are not recommended.
% of Ampere Rating | Opening Time |
110 % | 15min Minimum |
125 % | 1hr Maximum |
200 % | 12sec Minimum 4min Maximum |
*2 SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.