Unit Specifications
The following table provides electrical and refrigeration specifications for the HC101,121,151 Series Air Conditioners.
Nominal Capacity Rating: 10,000 BTUH
Standard Maximum Ambient: 131°F
Model | Operating Voltage Range
(Volts) |
Inrush Current (Start Up Current)(Amps) |
Loading Current (Running Current)(Amps) |
SCCR (Short Circuit Current Rating)(Amps) |
Recommended Circuit Protection (Amps) |
KVA Rating
(K-Watts) |
Refrig. Type | Refrig. Amount
(ounces) |
Low/High Unit Pressures
(psi) |
Noise Level(dBA) |
Weight (Unit/ Ship(lbs) |
HC101126 | 108-132 | 64.50 | 19.4 | *2 | 35Amp Class CC, CCMR Time Delay * | 2.3 | MO99 | 31.00 | 144 / 385 | 71.6 | 162/183 |
HC101236 | 207-253 | 31.50 | 8.20 | *2 | 15Amp Class CC, CCMR Time Delay * | 2.0 | MO99 | 31.00 | 155 / 322 | 71.6 | 165/186 |
HC101486 | 440-480 | 15.09 | 3.93 | 160K | 8Amp Class CC, CCMR Time Delay * | 2.0 | MO99 | 31.00 | 155 / 322 | 71.6 | 222/244 |
* Time-delay Fuses with the following electrical characteristics are recommended. Fast-acting fuses are not recommended.
% of Ampere Rating | Opening Time |
110 % | 15min Minimum |
125 % | 1hr Maximum |
200 % | 12sec Minimum, 4min Maximum |
*2 SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.
Model | Fan Air Flow (Evaporator Only) |
All | 667 CFM |
HC121 Series
Nominal Capacity Rating: 12,000 BTUH
Standard Maximum Ambient: 131°F
Model | Operating Voltage Range
(Volts) |
Inrush Current (Start Up Current)(Amps) |
Loading Current (Running Current)(Amps) |
SCCR (Short Circuit Current Rating)(Amps) |
Recommended Circuit Protection (Amps) |
KVA Rating
(K-Watts) |
Refrig. Type | Refrig. Amount
(ounces) |
Low/High Unit Pressures
(psi) |
Noise Level(dBA) |
Weight (Unit/ Ship(lbs) |
HC121126 | 108-132 | 64.50 | 19.4 | *2 | 35Amp Class CC, CCMR Time Delay * | 2.3 | MO99 | 38.00 | 144 / 385 | 71.6 | 162/183 |
HC121236 | 207-253 | 31.50 | 8.20 | *2 | 15Amp Class CC, CCMR Time Delay * | 2.0 | MO99 | 38.00 | 155 / 322 | 71.6 | 165/186 |
HC121486 | 440-480 | 15.09 | 3.93 | 160K | 8Amp Class CC, CCMR Time Delay * | 2.0 | MO99 | 38.00 | 155 / 322 | 71.6 | 222/244 |
HC151 Series
Nominal Capacity Rating: 15,000 BTUH
Standard Maximum Ambient: 131°F
Model | Operating Voltage Range
(Volts) |
Inrush Current (Start Up Current)(Amps) |
Loading Current (Running Current)(Amps) |
SCCR (Short Circuit Current Rating)(Amps) |
Recommended Circuit Protection (Amps) |
KVA Rating
(K-Watts) |
Refrig. Type | Refrig. Amount
(ounces) |
Low/High Unit Pressures
(psi) |
Noise Level(dBA) |
Weight (Unit/ Ship(lbs) |
HC151236 | 207-253 | 43.50 | 11.3 | *2 | 20Amp Class CC, CCMR Time Delay * | 2.6 | MO99 | 36.5 | 155 / 343 | 71.6 | 170/191 |
HC151486 | 440-480 | 20.84 | 5.41 | 160K | 12Amp Class CC, CCMR Time Delay * | 2.6 | MO99 | 36.5 | 188 / 395 | 71.6 | 234/256 |
* Time-delay Fuses with the following electrical characteristics are recommended. Fast-acting fuses are not recommended.
% of Ampere Rating | Opening Time |
110 % | 15min Minimum |
125 % | 1hr Maximum |
200 % | 12sec Minimum, 4min Maximum |
*2 SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.
Model | Fan Air Flow (Evaporator Only) |
All | 667 CFM |