Unit Specifications
HC121
Nominal Capacity Rating: 12,000 BTUH
Standard Maximum Ambient: 131°F
Model | Operating Voltage Range
(Volts) |
Inrush Current (Start Up Current) (Amps) |
Loading Current (Running Current) (Amps) |
SCCR (Short Circuit Current Rating) (Amps) |
Recommended Circuit Protection (Amps) |
KVA Rating
(K-Watts) |
Refrigerant Type | Refrigerant Amount
(ounces) |
Low/High Unit Pressures
(psi) |
Noise Level (dBA) |
Weight (Unit/Ship (lbs) |
HC121125 | 108-132 | 39 | 14 | * | 20 Amp Class CC, CCMR Time Delay * | 1.7 | MO99 | 38.00 | 155 / 322 | 71.6 | 165/186 |
* Time-delay Fuses with the following electrical characteristics are recommended. Fast-acting fuses are not recommended.
% of Ampere Rating | Opening Time |
110 % | 15min Minimum |
125 % | 1hr Maximum |
200 % | 12sec Minimum, 4min Maximum |
* SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.
Model | Fan Air Flow (Evaporator Only) |
HC121125 | 556 CFM |