What are the Unit Specifications for NE050, NE060, and N080?

Unit Specifications

The following table provides electrical and refrigeration specifications for the NE050, NE060 & NE080 Series Air Conditioners.

            NE050Series

Nominal Capacity Rating: 5,000 BTUH
Standard Maximum Ambient: 125°F
Unit Weight: 100lbs (120/230VAC) / 140lbs (480VAC)

Model Operating Voltage Range

(Volts)

Inrush Current
(Start Up Current)

(Amps)

Loading Current
(Running Current)

(Amps)

SCCR
(Short Circuit Current Rating)

(Amps)

Recommended Fuse Selection

(Amps)

KVA Rating

(K-Watts)

Refrigerant Type Refrigerant Amount

(ounces)

Low/High Unit  Pressures

(psi)

NE050126 110-120 23.42 7.26 *2 12 Amp Class CC, CCMR Time Delay * 0.85 R422d 12.50 188 / 300
NE050236 220-240 19.15 3.76 *2 10 Amp Class CC, CCMR Time Delay * 0.7 R422d 12.50 188 / 390
NE050486 440-480 9.18 1.44 160K 5 Amp Class CC, CCMR Time Delay * 0.7 R422d 12.50 188 / 390

* Time-delay Fuses with the following electrical characteristics are recommended.  Fast-acting fuses are not recommended.

% of Ampere Rating Opening Time
110 % 15min Minimum
125 % 1hr Maximum
200 % 12sec Minimum
4min Maximum

*2  SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.
            NE060 Series

Nominal Capacity Rating: 6,000 BTUH
Standard Maximum Ambient: 125°F
Unit Weight: 100lbs (120/230VAC) / 140lbs (480VAC)

Model Operating Voltage Range

(Volts)

Inrush Current
(Start Up Current)

(Amps)

Loading Current
(Running Current)

(Amps)

SCCR
(Short Circuit Current Rating)

(Amps)

Recommended Fuse Selection

(Amps)

KVA Rating

(K-Watts)

Refrigerant Type Refrigerant Amount

(ounces)

Low/High Unit  Pressures

(psi)

NE060126 110-120 42.41 7.83 *2 25 Amp Class CC, CCMR Time Delay * 1.0 R422d 18.00 188 / 340
NE060236 220-240 21.15 4.80 *2 12 Amp Class CC, CCMR Time Delay * 0.9 R422d 18.00 188 / 410
NE060486 440-480 10.13 1.80 160K 5 Amp Class CC, CCMR Time Delay * 0.9 R422d 18.00 188 / 410

            NE080 Series

Nominal Capacity Rating: 8,000 BTUH
Standard Maximum Ambient: 125°F
Unit Weight: 100lbs (120/230VAC) / 140lbs (480VAC)

Model Operating Voltage Range

(Volts)

Inrush Current
(Start Up Current)

(Amps)

Loading Current
(Running Current)

(Amps)

SCCR
(Short Circuit Current Rating)

(Amps)

Recommended Fuse Selection

(Amps)

KVA Rating

(K-Watts)

Refrigerant Type Refrigerant Amount

(ounces)

Low/High Unit  Pressures

(psi)

NE080126 110-120 42.41 7.83 *2 25 Amp Class CC, CCMR Time Delay * 1.0 R422d 19.00 188 / 345
NE080236 220-240 21.15 4.80 *2 12 Amp Class CC, CCMR Time Delay * 0.9 R422d 19.00 188 / 410
NE080486 440-480 10.13 1.80 160K 5 Amp Class CC, CCMR Time Delay * 0.9 R422d 19.00 188 / 410

* Time-delay Fuses with the following electrical characteristics are recommended.  Fast-acting fuses are not recommended.

% of Ampere Rating Opening Time
110 % 15min Minimum
125 % 1hr Maximum
200 % 12sec Minimum, 4min Maximum

*2  SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.