What are the Unit Specifications for NE050 and NE060 50Hz?

Unit Specifications

The following table provides electrical and refrigeration specifications for the NE050 & NE060 Series Air Conditioners.

NE050 Series

Nominal Capacity Rating: 5,000 BTUH
Standard Maximum Ambient: 125°F
Unit Weight: 100lbs (230VAC) / 140lbs (480VAC)

Model Operating Voltage Range

(Volts)

Inrush Current
(Start Up Current)

(Amps)

Loading Current
(Running Current)

(Amps)

SCCR
(Short Circuit Current Rating)

(Amps)

Recommended Fuse Selection

(Amps)

KVA Rating

(K-Watts)

Refrigerant Type Refrigerant Amount

(ounces)

Low/High Unit  Pressures

(psi)

NE050235 220-240 11.15 3.8 *2 6 Amp Class CC, CCMR Time Delay * 0.7 R422d 12.50 188 / 390
NE050485 440-480 5.6 1.9 160K 3 Amp Class CC, CCMR Time Delay * 0.7 R422d 12.50 188 / 390

* Time-delay Fuses with the following electrical characteristics are recommended.  Fast-acting fuses are not recommended.

% of Ampere Rating Opening Time
110 % 15min Minimum
125 % 1hr Maximum
200 % 12sec Minimum
4min Maximum

*2  SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.
           
NE060 Series

Nominal Capacity Rating: 6,000 BTUH
Standard Maximum Ambient: 125°F
Unit Weight: 100lbs (230VAC) / 140lbs (480VAC)

Model Operating Voltage Range

(Volts)

Inrush Current
(Start Up Current)

(Amps)

Loading Current
(Running Current)

(Amps)

SCCR
(Short Circuit Current Rating)

(Amps)

Recommended Fuse Selection

(Amps)

KVA Rating

(K-Watts)

Refrigerant Type Refrigerant Amount

(ounces)

Low/High Unit  Pressures

(psi)

NE060235 220-240 13.15 5.2 *2 7 Amp Class CC, CCMR Time Delay * 0.9 R422d 18.00 188 / 410
NE060485 440-480 6.6 2.6 160K 4 Amp Class CC, CCMR Time Delay * 0.9 R422d 18.00 188 / 410

* Time-delay Fuses with the following electrical characteristics are recommended.  Fast-acting fuses are not recommended.

% of Ampere Rating Opening Time
110 % 15min Minimum
125 % 1hr Maximum
200 % 12sec Minimum, 4min Maximum

*2  SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.