What are the Unit Specifications for NE020, NE030, and NE040?

Unit Specifications

The following table provides electrical and refrigeration specifications for the NE020, NE030 & NE040 Series Air Conditioners.

            NE020Series

Nominal Capacity Rating: 2,000 BTUH
Standard Maximum Ambient: 125°F
Unit Weight: 99lbs (120/230VAC) / 123lbs (480VAC)

Model Operating Voltage Range

(Volts)

Inrush Current
(Start Up Current)

(Amps)

Loading Current
(Running Current)

(Amps)

SCCR
(Short Circuit Current Rating)

(Amps)

Recommended Fuse Selection

(Amps)

KVA Rating

(K-Watts)

Refrigerant Type Refrigerant Amount

(ounces)

Low/High Unit  Pressures

(psi)

NE020126 110-120 16.42 3.76 *2 8 Amp Class CC, CCMR Time Delay * 0.5 R422d 10.25 188 / 300
NE020236 220-240 13.41 3.07 *2 6 Amp Class CC, CCMR Time Delay * 0.7 R422d 9.75 188 / 300
NE020486 440-480 4.11 0.93 160K 2 Amp Class CC, CCMR Time Delay * 0.5 R422d 10.25 188 / 300

* Time-delay Fuses with the following electrical characteristics are recommended.  Fast-acting fuses are not recommended.

% of Ampere Rating Opening Time
110 % 15min Minimum
125 % 1hr Maximum
200 % 12sec Minimum
4min Maximum

*2  SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.
            NE030 Series

Nominal Capacity Rating: 3,000 BTUH
Standard Maximum Ambient: 125°F
Unit Weight: 99lbs (120/230VAC) / 123lbs (480VAC)

Model Operating Voltage Range

(Volts)

Inrush Current
(Start Up Current)

(Amps)

Loading Current
(Running Current)

(Amps)

SCCR
(Short Circuit Current Rating)

(Amps)

Recommended Fuse Selection

(Amps)

KVA Rating

(K-Watts)

Refrigerant Type Refrigerant Amount

(ounces)

Low/High Unit  Pressures

(psi)

NE030126 110-120 23.42 5.15 *2 12 Amp Class CC, CCMR Time Delay * 0.7 R422d 10.25 188 / 300
NE030236 220-240 13.65 3.07 *2 7 Amp Class CC, CCMR Time Delay * 0.7 R422d 9.75 188 / 375
NE030486 440-480 5.86 1.51 160K 3 Amp Class CC, CCMR Time Delay * 0.75 R422d 10.25 188 / 300

            NE040 Series

Nominal Capacity Rating: 4,000 BTUH
Standard Maximum Ambient: 125°F
Unit Weight: 99lbs (120/230VAC) / 123lbs (480VAC)

Model Operating Voltage Range

(Volts)

Inrush Current
(Start Up Current)

(Amps)

Loading Current
(Running Current)

(Amps)

SCCR
(Short Circuit Current Rating)

(Amps)

Recommended Fuse Selection

(Amps)

KVA Rating

(K-Watts)

Refrig. Type Refrig. Amount

(ounces)

Low/High Unit  Pressures

(psi)

NE040126 110-120 23.42 5.53 *2 12 Amp Class CC, CCMR Time Delay * 0.7 R422d 10.25 188 / 345
NE040236 220-240 13.65 3.07 *2 7 Amp Class CC, CCMR Time Delay * 0.7 R422d 9.75 188 / 375
NE040486 440-480 5.86 1.51 160K 3 Amp Class CC, CCMR Time Delay * 0.75 R422d 10.25 188 / 345

* Time-delay Fuses with the following electrical characteristics are recommended.  Fast-acting fuses are not recommended.

% of Ampere Rating Opening Time
110 % 15min Minimum
125 % 1hr Maximum
200 % 12sec Minimum, 4min Maximum

*2  SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.