What are the Unit Specifications for HC101, HC121, and HC151?

Unit Specifications

The following table provides electrical and refrigeration specifications for the HC101,121,151 Series Air Conditioners.

            HC101 Series

Nominal Capacity Rating: 10,000 BTUH
Standard Maximum Ambient: 131°F

Model Operating Voltage Range

(Volts)

Inrush Current
(Start Up Current)(Amps)
Loading Current
(Running Current)(Amps)
SCCR
(Short Circuit Current Rating)(Amps)
Recommended
Circuit Protection

(Amps)

KVA Rating

(K-Watts)

Refrig. Type Refrig. Amount

(ounces)

Low/High Unit  Pressures

(psi)

Noise
Level(dBA)
Weight
(Unit/ Ship(lbs)
HC101126 108-132 64.50 19.4 *2 35Amp Class CC, CCMR Time Delay * 2.3 MO99 31.00 144 / 385 71.6 162/183
HC101236 207-253 31.50 8.20 *2 15Amp Class CC, CCMR Time Delay * 2.0 MO99 31.00 155 / 322 71.6 165/186
HC101486 440-480 15.09 3.93 160K 8Amp Class CC, CCMR Time Delay * 2.0 MO99 31.00 155 / 322 71.6 222/244

* Time-delay Fuses with the following electrical characteristics are recommended.  Fast-acting fuses are not recommended.

% of Ampere Rating Opening Time
110 % 15min Minimum
125 % 1hr Maximum
200 % 12sec Minimum, 4min Maximum

*2  SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.

Model Fan Air Flow (Evaporator Only)
All 667 CFM

            HC121 Series

Nominal Capacity Rating: 12,000 BTUH
Standard Maximum Ambient: 131°F

Model Operating Voltage Range

(Volts)

Inrush Current
(Start Up Current)(Amps)
Loading Current
(Running Current)(Amps)
SCCR
(Short Circuit Current Rating)(Amps)
Recommended
Circuit Protection

(Amps)

KVA Rating

(K-Watts)

Refrig. Type Refrig. Amount

(ounces)

Low/High Unit  Pressures

(psi)

Noise
Level(dBA)
Weight
(Unit/ Ship(lbs)
HC121126 108-132 64.50 19.4 *2 35Amp Class CC, CCMR Time Delay * 2.3 MO99 38.00 144 / 385 71.6 162/183
HC121236 207-253 31.50 8.20 *2 15Amp Class CC, CCMR Time Delay * 2.0 MO99 38.00 155 / 322 71.6 165/186
HC121486 440-480 15.09 3.93 160K 8Amp Class CC, CCMR Time Delay * 2.0 MO99 38.00 155 / 322 71.6 222/244

            HC151 Series

Nominal Capacity Rating: 15,000 BTUH
Standard Maximum Ambient: 131°F

Model Operating Voltage Range

(Volts)

Inrush Current
(Start Up Current)(Amps)
Loading Current
(Running Current)(Amps)
SCCR
(Short Circuit Current Rating)(Amps)
Recommended
Circuit Protection

 

(Amps)

KVA Rating

(K-Watts)

Refrig. Type Refrig. Amount

(ounces)

Low/High Unit  Pressures

(psi)

Noise
Level(dBA)
Weight
(Unit/ Ship(lbs)
HC151236 207-253 43.50 11.3 *2 20Amp Class CC, CCMR Time Delay * 2.6 MO99 36.5 155 / 343 71.6 170/191
HC151486 440-480 20.84 5.41 160K 12Amp Class CC, CCMR Time Delay * 2.6 MO99 36.5 188 / 395 71.6 234/256

* Time-delay Fuses with the following electrical characteristics are recommended.  Fast-acting fuses are not recommended.

% of Ampere Rating Opening Time
110 % 15min Minimum
125 % 1hr Maximum
200 % 12sec Minimum, 4min Maximum

*2  SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.

Model Fan Air Flow (Evaporator Only)
All 667 CFM