What are the HC080 Unit Specifications?

Unit Specifications

            HC080

Nominal Capacity Rating: 8,000 BTUH
Standard Maximum Ambient: 125°F

Model Operating Voltage Range

(Volts)

Inrush Current
(Start Up Current)(Amps)
Loading Current
(Running Current)(Amps)
SCCR
(Short Circuit Current Rating)(Amps)
Recommended
Circuit Protection(Amps)
KVA Rating

(K-Watts)

Refrigerant Type Noise
Level(dBA)
Weight
(Unit/Ship(lbs)
HC080235 207-253 18.7 6.5 *2 10 Amp Class CC, CCMR Time Delay * 1.5 MO99 71.6 165/186

* Time-delay Fuses with the following electrical characteristics are recommended.  Fast-acting fuses are not recommended.

% of Ampere Rating Opening Time
110 % 15min Minimum
125 % 1hr Maximum
200 % 12sec Minimum, 4min Maximum

*2  SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.

Model Fan Air Flow (Evaporator Only)
HC080235 556 CFM