What are the Unit Specifications for A2A Heat Exchangers?

Unit Specifications
The following table provides electrical specifications for the Thermal Edge A2A Compact, Slim, Deep, & Tall Series Heat Exchangers

A2AC – Compact Series

Standard Maximum Ambient: 160°F
Unit Weight: 20lbs
Mounting Dimensions (H x W x D):  16.5” x 11” x 3.5”

Model

Operating Voltage Range

(Volts)

Inrush Current

(Startup Current)

(Amps)

Loading Current

(Running Current)

(Amps)

SCCR

(Short Circuit Current Rating)

(Amps)

Rec. Circuit Protection Device Rating

(Amps)

VA Rating

(Watts)

Refrig. Type

(amount in oz)

Watt/
°C

Free Air Flow

(CFM)

A2AC040120 110-120 1.92 0.35 *2 1.5 Amp* 42 CH3OH
(0.41)
11 131
A2AC040230 220-240 1.65 0.18 *2 1 Amp* 42 CH3OH
(0.41)
11 131
A2AC040D24 21.6-26.4 3.90 0.80 *2 2.5 Amp* 20 CH3OH
(0.41)
11 127
A2AC040D48 43.2-52.8 2.00 0.40 *2 1.25 Amp* 20 CH3OH
(0.41)
11 127
A2AC080120 110-120 1.92 0.35 *2 1.5 Amp* 42 CH3OH
(0.41)
22 131
A2AC080230 220-240 1.65 0.18 *2 1 Amp* 42 CH3OH
(0.41)
22 131
A2AC080D24 21.6-26.4 3.90 0.80 *2 2.5 Amp* 20 CH3OH
(0.41)
22 127
A2AC080D48 43.2-52.8 2.00 0.40 *2 1.25 Amp* 20 CH3OH
(0.41)
22 127

* Fast Acting Fuses with the following electrical characteristics are recommended. Do not use Extremely Fast Acting Fuse.

% of Ampere Rating Opening Time
100 % None
135 % 60min Maximum
200 % 120sec Maximum

*2  SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 10KA for Fast Acting Fuses.

A2AS – Slim Series

Standard Maximum Ambient: 160°F
Unit Weight: 28lbs
Mounting Dimensions (H x W x D):  21.0” x 5.6” x 11.0”

Model

Operating Voltage Range

(Volts)

Inrush Current

(Startup Current)

(Amps)

Loading Current

(Running Current)

(Amps)

SCCR

(Short Circuit Current Rating)

(Amps)

Rec. Circuit Protection Device Rating

(Amps)

VA Rating

(Watts)

Refrig. Type

(amount in oz)

Watt/
°C

Free Air Flow

(CFM)

A2AS040120 110-120 1.92 0.35 *2 1.5 Amp* 42 CH3OH
(0.81)
11 131
A2AS040230 220-240 1.65 0.18 *2 1 Amp* 42 CH3OH
(0.81)
11 131
A2AS040D24 21.6-26.4 3.90 0.80 *2 2.5 Amp* 20 CH3OH
(0.81)
11 127
A2AS040D48 43.2-52.8 2.00 0.40 *2 1.25 Amp* 20 CH3OH
(0.81)
11 127
A2AS080120 110-120 1.92 0.35 *2 1.5 Amp* 42 CH3OH
(0.81)
22 131
A2AS080230 220-240 1.65 0.18 *2 1 Amp* 42 CH3OH
(0.81)
22 131
A2AS080D24 21.6-26.4 3.90 0.80 *2 2.5 Amp* 20 CH3OH
(0.81)
22 127
A2AS080D48 43.2-52.8 2.00 0.40 *2 1.25 Amp* 20 CH3OH
(0.81)
22 127
A2AS120120 110-120 1.92 0.35 *2 1.5 Amp* 42 CH3OH
(0.81)
33 131
A2AS120230 220-240 1.65 0.18 *2 1 Amp* 42 CH3OH
(0.81)
33 131
A2AS120D24 21.6-26.4 3.90 0.80 *2 2.5 Amp* 20 CH3OH
(0.81)
33 127
A2AS120D48 43.2-52.8 2.00 0.40 *2 1.25 Amp* 20 CH3OH
(0.81)
33 127
A2AS160120 110-120 1.92 0.35 *2 1.5 Amp* 42 CH3OH
(0.81)
44 131
A2AS160230 220-240 1.65 0.18 *2 1 Amp* 42 CH3OH
(0.81)
44 131
A2AS160D24 21.6-26.4 3.90 0.80 *2 2.5 Amp* 20 CH3OH
(0.81)
44 127
A2AS160D48 43.2-52.8 2.00 0.40 *2 1.25 Amp* 20 CH3OH
(0.81)
44 127

A2AD – Deep Series

Standard Maximum Ambient: 160°F
Unit Weight: 24lbs
Mounting Dimensions (H x W x D):  16.5” x 11” x 5.5”

Model

Operating Voltage Range

(Volts)

Inrush Current

(Startup Current)

(Amps)

Loading Current

(Running Current)

(Amps)

SCCR

(Short Circuit Current Rating)

(Amps)

Rec. Circuit Protection Device Rating

(Amps)

VA Rating

(Watts)

Refrig. Type

(amount in oz)

Watt/
°C

Free Air Flow

(CFM)

A2AD120120 110-120 1.92 0.35 *2 1.5 Amp* 42 CH3OH
(0.81)
33 131
A2AD120230 220-240 1.65 0.18 *2 1 Amp* 42 CH3OH
(0.81)
33 131
A2AD120D24 21.6-26.4 3.90 0.80 *2 2.5 Amp* 20 CH3OH
(0.81)
33 127
A2AD120D48 43.2-52.8 2.00 0.40 *2 1.25 Amp* 20 CH3OH
(0.81)
33 127
A2AD160120 110-120 1.92 0.35 *2 1.5 Amp* 42 CH3OH
(0.81)
44 131
A2AD160230 220-240 1.65 0.18 *2 1 Amp* 42 CH3OH
(0.81)
44 131
A2AD160D24 21.6-26.4 3.90 0.80 *2 2.5 Amp* 20 CH3OH
(0.81)
44 127
A2AD160D48 43.2-52.8 2.00 0.40 *2 1.25 Amp* 20 CH3OH
(0.81)
44 127

* Fast Acting Fuses with the following electrical characteristics are recommended.  Do not use Extremely Fast Acting Fuse.

% of Ampere Rating Opening Time
100 % None
135 % 60min Maximum
200 % 120sec Maximum

*2  SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 10KA for Fast Acting Fuses.

A2AT – Tall Series

Standard Maximum Ambient: 160°F
Unit Weight: 36lbs
Mounting Dimensions (H x W x D):  29.0” x 13.88” x 5.5”

Model

Operating Voltage Range

(Volts)

Inrush Current

(Startup Current)

(Amps)

Loading Current

(Running Current)

(Amps)

SCCR

(Short Circuit Current Rating)

(Amps)

Rec. Circuit Protection Device Rating

(Amps)

VA Rating

(Watts)

Refrig. Type

(amount in oz)

Watt/
°C

Free Air Flow

(CFM)

A2AT200120 110-120 2.59 0.47 *2 2 Amp* 56 CH3OH
(1.22)
55 211
A2AT200230 220-240 1.32 0.24 *2 1 Amp* 56 CH3OH
(1.22)
55 211
A2AT200D24 21.6-26.4 9.7 1.94 *2 6 Amp* 47 CH3OH
(1.22)
55 235
A2AT200D48 43.2-52.8 4.8 0.96 *2 3 Amp* 47 CH3OH
(1.22)
55 235
A2AT260120 110-120 2.59 0.47 *2 2 Amp* 56 CH3OH
(1.22)
72 211
A2AT260230 220-240 1.32 0.24 *2 1 Amp* 56 CH3OH
(1.22)
72 211
A2AT260D24 21.6-26.4 9.7 1.94 *2 6 Amp* 47 CH3OH
(1.22)
72 235
A2AT260D48 43.2-52.8 4.8 0.96 *2 3 Amp* 47 CH3OH
(1.22)
72 235

* Fast Acting Fuses with the following electrical characteristics are recommended.  Do not use Extremely Fast Acting Fuse.

% of Ampere Rating Opening Time
100 % None
135 % 60min Maximum
200 % 120sec Maximum

*2  SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per UL50 & UL508a to protect the AC unit. Typically 10KA for Fast Acting Fuses.